Item |
1MW/2.0MWh |
1.1 MW/2.2MWh |
| DC Data | ||
Battery Chemistry |
Lithium-Iron Phosphate (LFP) |
|
Cell Life Cycle |
80% Retention with 5,000 Cycles 0.5C ~ 25°C |
|
Cell spec |
3.2V / 280Ah |
|
String Configuration |
1P 384S |
1P 416S |
Number of Strings |
6 |
|
Rated Energy Capacity |
2MWh |
2.2 MWh |
DC Rated Energy Capacity |
2,064.36 kWh |
2,236.44 kWh |
Rated Voltage |
1,228.8V |
1,331.2V |
Voltage Range |
1,075.2V ~ 1,363.2V |
1,164.8V ~ 1,476.8V |
BMS Communication Interface |
RS485, Ethernet |
|
BMS Communication Protocol |
Modbus RTU, Modbus TCP |
|
| AC Data | ||
Rated AC Power |
1,000 kW |
1,100 kW |
Maximum AC Power |
1,320 kW |
|
Rated Voltage |
690V |
|
Grid Voltage Range |
586.5 ~ 759V (Optional) |
|
AC Rate of Current |
836.8A |
920.5A |
Output THDi |
< 3% |
|
AC PF |
0.1 ~ 1 leading or lagging (controllable) |
|
AC Output |
Three-phase and three-wire |
|
| General Data | ||
Dimension w/o clearances (L*W*H) |
6058 x 2438 x 2591 mm |
6058 x 2438 x 2896 mm |
Weight of the whole system |
24t |
25.5t |
Degree of protection |
IP65 |
|
Operating Temperature range |
-20 ~ 40°C |
|
Relative Humidity |
0 ~ 95% (non-condensing) |
|
Max Working Altitude |
4,000 m / 13,123 ft |
|
Cooling concept of DC Hatch |
HVAC |
|
Fire Fighting System |
NOVEC1230 / FM-200 |
|
Communication Interfaces |
RS485, Ethernet, GPRS |
|
Certificates |
UL9540, IEC62619, IEC62109, IEC62933, UN3536, etc. |
|